Schematex
sld·IEC 60364 / EN 61439-3·residential·complexity 2/3

Residential consumer unit — generic IEC 60364

Generic European residential consumer unit per IEC 60364 / EN 61439-3 — service head, isolator, type-AC main RCD, and per-circuit MCBs for lighting, sockets, kitchen, water heater, EV charger (with type-B RCBO), and outdoor circuit.

For the European domestic installer

Open in Playground →
SLD·§ IEEE 315-1975
↘ preview
100%
Residential Consumer Unit — IEC 60364 Single-line diagram with 19 nodes and 18 connections Residential Consumer Unit — IEC 60364 230V 230V 1.5 mm² Cu PVC 2.5 mm² Cu PVC 2.5 mm² Cu PVC 4 mm² Cu PVC 4 mm² Cu PVC 6 mm² Cu XLPE 2.5 mm² Cu XLPE Service head 230V/63A 230V Wh kWh meter Main isolator 63A 6kA GFI Main RCD 63A / 30mA Type AC 230V · Consumer-unit busbar MCB lighting 6A B-curve MCB sockets ground floor 16A B-curve MCB sockets first floor 16A B-curve MCB kitchen ring 20A C-curve MCB water heater 20A C-curve GFI RCBO EV charger 32A / 30mA Type B MCB outdoor 10A B-curve Lighting circuit Sockets — ground floor Sockets — first floor Kitchen ring final Water heater 4.5 kW EV charger 7.4 kW Mode 3 Outdoor / garden
UTF-8 · LF · 38 lines · 1496 chars✓ parsed·8.5 ms·12.1 KB SVG

Scenario

A domestic electrical installer in any IEC 60364 jurisdiction — France (NF C 15-100), Germany (DIN VDE 0100), the United Kingdom (BS 7671), Italy (CEI 64-8), Australia / New Zealand (AS/NZS 3000), and most of the rest of the world outside the NEC — files this single-line as part of the Certificat de Conformité / Elektroinstallationsattest / Electrical Installation Condition Report required after a new installation or major alteration. EN 61439-3 is the European harmonized standard for Distribution Boards intended to be operated by Ordinary persons (DBO), and IEC 60364-4-41 governs the protection-against-shock chain (isolation → 30 mA RCD → branch protection). Unlike NEC residential practice where the panel lives as a leaf on the SLD with internals on a separate panel schedule, the IEC 60364 single-line is expected to expand the consumer unit's internal protection chain.

Annotation key

How to read

The service head delivers single-phase 230 V at the cut-out fuse rating (63 A here). The kWh meter records consumption, then the main isolator gives a single-action means of disconnecting the entire installation for maintenance. Downstream of the isolator the main RCD provides shock protection at 30 mA Type AC for the bulk of branch circuits; from the consumer-unit busbar, six MCBs feed lighting, two socket circuits, a kitchen ring, a water heater, and an outdoor circuit. The EV charger does not share the main RCD — IEC 60364-7-722 requires a Type B RCBO on the charger circuit because the Mode-3 charge controller can produce smooth DC residual currents that a Type AC RCD cannot detect, leaving people unprotected against shock during a DC fault. Cable sizes scale with the MCB rating per the relevant national reference method (1.5 mm² for 6 A lighting, 2.5 mm² for 16 A sockets, 4 mm² for 20 A kitchen / heater, 6 mm² for the 32 A EV charger). An inspector reads the diagram top-down to verify the protection chain and the discrimination between the main RCD and the EV-circuit RCBO.

SLD syntax